Stulz Computer Room Air Conditioning (CRAC) CyberRow Row-based Cooling Solution
CyberRow is an advanced precision A/C unit, which is tailor-made for the
targeted cooling of racks. In the CyberRow, innovative air conduction has been
enhanced by state-of-the-art technology, which enhances the performance,
flexibility and efficiency. Fluctuating server rack loads, space restrictions,
lack of a raised floor, existing server technology - these are some of the
tricky situations in everyday practice that the CyberRow has been specially
developed to deal with.
CyberRow is a standalone A/C unit and is installed and operated independently
from the rack. This complete separation of the rack and the A/C unit increases
reliability and provides greater freedom for designing the layout in the data
centre.
CyberRow is available with 2 sizes and 4 different cooling systems:
- CW-System (chilled water cooling)
- A-System (direct expansion)
- G-System (direct expansion and plate condenser)
- GE-System (direct expansion with indirect free cooling)
Features & Benefits
|
Features
|
Benefits
|
| Horizontal air conduction |
The cold air reaches the rack via the
shortest route |
| Electronic control |
Monitors and controls all components inside
and outside the A/C unit that are needed to
generate cold air |
| 3 EC fans |
Independent, infinitely adjustable EC fans
ensure maximum efficiency |
| EC compressor |
Infinitely adjustable for precise cooling
capacity and 50% lower power consumption when
starting the compressor, thanks to soft start
function |
| Electronic expansion value |
Finely controls the cooling capacity within a
few seconds |
| Flexibility and compatibility |
The CyberRow is available in 4 different
cooling systems (A, CW, G, and as a GE system
with Indirect Fee Cooling) and in 2 sizes |
| Modernizing cooling systems in existing
buildings |
Thanks to its compact size and universal
suitability for racks from different
manufacturers, the CyberRow can also be used
without need to modernize cooling system in
existing buildings |
Back to the Top
CyberRow Features
| Feature / System |
CW |
DX |
G |
GE |
| EC Fans |
 |
 |
 |
 |
| EC Compressor |
|
 |
 |
 |
| Electronic Expansion Valve |
|
 |
 |
 |
| Zig-zag Air Filter |
 |
 |
 |
 |
| C2020 |
 |
 |
 |
 |
| C7000 |
|
|
|
 |
| Free Cooling |
|
|
|
 |
| 2-way Valve |
 |
|
|
|
Technical specification
| CyberRow |
DX Size 1 |
DX Size 2 |
CW Size 1 |
CW Size 2 |
| Unit Type |
EHMB4A |
EHMC7A |
EHMC2W |
EHME5W |
| Height (in mm) |
1,950 |
1,950 |
1,950 |
1,950 |
| Depth (in mm) |
1,175 |
1,175 |
1,175 |
1,175 |
| Width (in mm) |
400 |
600 |
400 |
600 |
| Cooling capacity (in kW) |
24.0 |
36.5 |
32.2 |
56.0 |
| Airflow (in m³/h) |
4,700 |
7,700 |
6,000 |
10,800 |
| Water flow - cooling (in l/h) |
n.a. |
n.a. |
5,540 |
9,630 |
CyberRow with Variable Capacity Control
Efficient IT plant runs 24/7, but the operational conditions in a Data Center
can change throughout the day. The CyberRow rack-coolers monitor and adapt the
cooling capacity to the local heat load. This avoids the under or over supply of
cooling in a particular area.
To learn more about PTS consulting services to support Air Conditioning
Equipment & Systems deployments and support,
contact us
or visit: